Our advanced fire protection system utilizes intelligent visual tools to detect and disgusting fire conditions and automatically direct a focused suppression foam to extinguish the fire with limited damage or impact to surrounding areas and assets.

DETECT.
TARGET. FIRE.

LASER RANGE FINDER

Mask Group 12

POWER CONSUMPTION

Input voltage 110/230V AC
System working voltage/consumption Up to 10 Amp @ 12V DC (Charging consumption)
Nominal Power Consumption 4Amp @ 24v DC
Battery backup power 12V or 120V AC according to customer requirement

SENSORS

Thermal Camera Field of View Vertical 54.50 Horizontal 73.20
Laser Rangefinder Range up to 260 ft x Resolution 0.39in

MONITOR GUN

Piping Pipe: 2”, Sleeve: 1.25’’
Nozzle 1” or 3/4”
Discharge premix 50 GPM
Discharge Finished foam 450 GPM per monitor
Eective discharge range 120 feet / 35 m (zero wind condition)

FIRE SYSTEM CONTROL

System control Programmable Logic Control

SYSTEM RESPONSE TIME

Fire detection 2 – 3 sec and up to 10 sec
Suppression (normal fire size app. 4 m / 43 ft ) 5 -10 sec and up to 22 sec
Monitor targeting 1 – 2 sec and up to 10 sec
Detection Flame parameter area sq. ft/m @ Range ft./m 1 sq. ft. /0.092 m @ 260 ft / 80 m

COMMUNITCATION

IP over Net. Internet supported protocols
Direct connecting tosystem (POE Switch) IP No. by using switch direct to PC or PLC

MANUAL DEPLOYMENT

Booster line on reel 1″ @ 100 ft

External line coupling with collapsible hose 1.5″ @ 100 ft